ARCOTRONICS.Net:F.LL.DU.040A.945.I0 Tubular Filter

  • This feed-thu filter provides excellent attenuation up to GHz frequencies. It is particularly suitable for UPS, high frequency welding machines, screened rooms, telecom, medical equipment, and various other applications. The high capacitance values require special protective measures (neutral line connections in accordance to VDE 0875 and VDE 100).
  • Internal Components Approved: UL 1283
  • Manufacture: metal case sealed with plastic cover; mounted with metrical nut.
  • Connections: thread bar with metric nut M6 (up to 63A), M8 (100A), M10 (200A); M12 (300A) on screwing the cable to the filter the lock nut must be held into position to avoid a torque to the threaded bar inside the filter.
  • Rated Voltage: 250Vac(50/60Hz) / 350 Vdc
  • Rated Current: 40 A
  • Voltage Test (2 s): 1075 Vdc
  • Climate Category: GPC (40/085/56); temp range -40c to +85c
  • Ref.-Std VDE0565-1-A C(uf)=2x4.7, Cl= X2
  • Pi configuration circuit
  • Typical loaded insertion loss (dB) = 90@1MHz, >100@10MHz, >100@100MHz
  • Dimensions (mm): A=39.5, B=166
  • Only $87.95 each (minimum order is 8 units)
  • Standard Lead-Time is 7 weeks ARO. However, this varies and your order confirmation will indicate the actual Lead-Time. An Additional Shipping/Handling Charge, based on your total order quantity, will be invoiced to you seperately.